Uncertainty management in fire risk analyses (URAN)

Jukka Vaari, Alexandra Tissari, Nikhil Verma, Simo Hostikka, Morteza Gholami Haghighi Fard

Tutkimustuotos: Artikkeli kirjassa/konferenssijulkaisussaChapterProfessional

Abstrakti

A pyrolysis modelling approach was expanded to full-scale simulation of a cable tray fire. Earlier experimental thermogravimetric analysis (TGA) and cone calorimeter results were used to construct the pyrolysis model. For model validation, data form the CFSS-1 experiment of the OECD/NEA PRISME 2 project was used.
A state-of-the-art methodology for the simulation of the cable cone calorimetry with FDS wass proposed in this study. Cable geometry was modelled with cubic obstructions using the new 3D heat transfer (HT3D) and 3D pyrolysis (PYRO3D) routines of the FDS.
Effects of ageing on the thermal decomposition process of polyethylene using united-atom MD simulations were studied. Qualitatively, ageing had a very little effect on the shape and position of the simulated TGA curves, suggesting essentially no effect of ageing on pyrolysis of polyethylene.
AlkuperäiskieliEnglanti
OtsikkoSAFIR2022 - The Finnish Research Programme on Nuclear Power Plant Safety 2019-2022
KustantajaVTT
Sivut119-133
ISBN (elektroninen)978-951-38-8743-8
TilaJulkaistu - 2021
OKM-julkaisutyyppiD2 Artikkeli ammatillisessa käyttöoppaassa tai oppaassa tai ammattilaistietojärjestelmässä tai käsikirjamateriaalissa

Julkaisusarja

NimiVTT Technology
Numero383
ISSN (elektroninen)2242-1211

Sormenjälki Sukella tutkimusaiheisiin 'Uncertainty management in fire risk analyses (URAN)'. Ne muodostavat yhdessä ainutlaatuisen sormenjäljen.