Modelling of room air temperature profile with displacement ventilation

Tutkimustuotos: Lehtiartikkelivertaisarvioitu

Tutkijat

Organisaatiot

  • Nanjing Tech University
  • Xi'an University of Architecture and Technology
  • Halton Oy
  • Beketov National University of Urban Economy

Kuvaus

An accurate temperature gradient calculation is essential for displacement ventilation (DV) system design, since it directly relates to the calculation of supply air flow rate. Several simplified nodal models were developed and implemented in the various building simulation programmes to estimate the temperature stratification in rooms with displacement ventilation. However, the most commonly used models do not take into account the types and locations of the heat loads in rooms with DV. As a result, the calculated air temperature in the occupied zone can defer from the real one by 2–3 °C, which causes poor thermal comfort and inadequate sizing of the ventilation and cooling systems.  In the present study, the nodal model was proposed to provide a simplified technique to predict the vertical temperature gradient in rooms with DV. In addition, the effect of the room height and locations of the indoor heat sources were studied for the typical office environment. The measurement data were compared with the existing nodal models and the proposed nodal model in terms of predicting the occupied zone temperatures. The presented nodal model demonstrates an accurate calculation of the temperature gradient for the typical heat loads and combinations of them.

Yksityiskohdat

AlkuperäiskieliEnglanti
JulkaisuInternational Journal of Ventilation
TilaJulkaistu - 27 maaliskuuta 2019
OKM-julkaisutyyppiA1 Julkaistu artikkeli, soviteltu

ID: 31308805