Integrated FDD system for valve stiction in a paperboard machine

Octavio Pozo Garcia, Vesa-Matti Tikkala, Alexey Zakharov, Sirkka-Liisa Jämsä-Jounela

Tutkimustuotos: LehtiartikkeliArticleScientificvertaisarvioitu

12 Sitaatiot (Scopus)
444 Lataukset (Pure)

Abstrakti

The performance of a modern industrial plant can be severely affected by the performance of its key devices, such as valves. In particular, valve stiction can cause poor performance in control loops and can consequently lower the efficiency of the plant and the quality of the product. This paper presents an integrated FDD system for valve stiction which employs various FDD methods in a parallel configuration. A reliability index was integrated into each method in order to estimate their degree of influence in the final diagnosis of the system. Each method and the integrated system were tested using industrial data.
AlkuperäiskieliEnglanti
Sivut818-828
JulkaisuControl Engineering Practice
Vuosikerta21
Numero6
DOI - pysyväislinkit
TilaJulkaistu - 2013
OKM-julkaisutyyppiA1 Alkuperäisartikkeli tieteellisessä aikakauslehdessä

Tutkimusalat

  • Fault detection and diagnosis; Valve; Oscillations; Shape analysis; Stiction; Industrial application

Sormenjälki

Sukella tutkimusaiheisiin 'Integrated FDD system for valve stiction in a paperboard machine'. Ne muodostavat yhdessä ainutlaatuisen sormenjäljen.