Demand response events in district heating : Results from field tests in a university building

Tutkimustuotos: Lehtiartikkeli

Tutkijat

Organisaatiot

  • University of California at Berkeley
  • Nanjing Tech University
  • Fidelix Ltd.
  • Granlund Oy

Kuvaus

Demand side management will play a major role in future energy systems. However, while they have been explored in some depth for electricity grids, a similar progress has not been made for district heating networks (DHN). To this end, the current work field-tested the effect of demand side management, in the form of price based, demand response (DR) events, in the DHN catering to a university building. Responding to variations in a pricing model, the temperature of inlet water was varied from the heating water substation. Using combinations of parameters, 11 different DR scenarios were executed. To gauge the effect of the DR interventions, inlet water temperature, room air temperature, and occupant satisfaction were monitored. Depending on the constraints imposed, significant variations in the inlet water temperature and peaks and drops in the room air temperature were noted. The different DR scenarios did not greatly alter occupant satisfaction levels. The study was able to provide useful data from field tests of DR events in a DHN. The data also showed that price based DR events may be triggered and executed without significantly impacting occupant satisfaction with thermal comfort of the premises.

Yksityiskohdat

AlkuperäiskieliEnglanti
Artikkeli101481
Sivumäärä13
JulkaisuSustainable Cities and Society
Vuosikerta47
TilaJulkaistu - 1 toukokuuta 2019
OKM-julkaisutyyppiA1 Julkaistu artikkeli, soviteltu

ID: 32385903