T1 - A new technique for fault diagnosis in transformer insulating oil based on infrared spectroscopy measurements
AU - Darwish, Mohamed M.F.
AU - Hassan, Mohamed H.A.
AU - Abdel-Gawad, Nagat M.K.
AU - Lehtonen, Matti
AU - Mansour, Diaa Eldin A.
N1 - Funding Information:
The authors thank the Science, Technology & Innovation Funding Authority (STIFA), Egypt, under a grant (31292) for their support.
Publisher Copyright:
© 2024 The Authors. High Voltage published by John Wiley & Sons Ltd on behalf of The Institution of Engineering and Technology and China Electric Power Research Institute.
PY - 2024/4
Y1 - 2024/4
N2 - Condition monitoring of the insulating system within power transformers has a massive importance according to the electrical utilities. Dissolved gas analysis (DGA) is frequently used for this purpose. However, DGA lacks the necessary level of accuracy to identify all equipment faults, particularly in their initial stages of degradation. Also, it does not have the capability for real-time monitoring and relies on manual sampling and laboratory testing, causing potential delays in fault identification. Additionally, the interpretation of DGA data necessitates specialised expertise, which may pose difficulties for smaller entities that have limited access to resources. Therefore, the contribution of this research is to use infrared spectroscopy measurements as a new effective technique substituting the DGA method for fault diagnosis in insulating oil. The inception faults that were considered in this study were the electrical fault (discharges of high energy) and the thermal fault (300°C < Temperature <700°C). Regarding that, two test cells were crafted especially for serving the simulation processes inside the laboratory for both types of inception faults. Subsequently, six samples of pure paraffinic mineral oil were taken to be degraded in the laboratory. Following that, all of them besides another sample that were not subjected to any kind of faults were taken to be examined by Fourier transform infrared (FTIR) spectroscopy to obtain an overview of the oil's behaviour in each fault case. After that, the FTIR analysis was initially verified utilising the DGA method. Then, for further affirmation, the dielectric dissipation factor (DDF) for all samples was measured. In the final analysis, the verification tests provide experimental evidence about the outperformance of this new optical technique in detecting the transformer's inception faults in addition to proving its potential for being a superior alternative to the well-known traditional diagnostic techniques.
AB - Condition monitoring of the insulating system within power transformers has a massive importance according to the electrical utilities. Dissolved gas analysis (DGA) is frequently used for this purpose. However, DGA lacks the necessary level of accuracy to identify all equipment faults, particularly in their initial stages of degradation. Also, it does not have the capability for real-time monitoring and relies on manual sampling and laboratory testing, causing potential delays in fault identification. Additionally, the interpretation of DGA data necessitates specialised expertise, which may pose difficulties for smaller entities that have limited access to resources. Therefore, the contribution of this research is to use infrared spectroscopy measurements as a new effective technique substituting the DGA method for fault diagnosis in insulating oil. The inception faults that were considered in this study were the electrical fault (discharges of high energy) and the thermal fault (300°C < Temperature <700°C). Regarding that, two test cells were crafted especially for serving the simulation processes inside the laboratory for both types of inception faults. Subsequently, six samples of pure paraffinic mineral oil were taken to be degraded in the laboratory. Following that, all of them besides another sample that were not subjected to any kind of faults were taken to be examined by Fourier transform infrared (FTIR) spectroscopy to obtain an overview of the oil's behaviour in each fault case. After that, the FTIR analysis was initially verified utilising the DGA method. Then, for further affirmation, the dielectric dissipation factor (DDF) for all samples was measured. In the final analysis, the verification tests provide experimental evidence about the outperformance of this new optical technique in detecting the transformer's inception faults in addition to proving its potential for being a superior alternative to the well-known traditional diagnostic techniques.
UR - http://www.scopus.com/inward/record.url?scp=85183172739&partnerID=8YFLogxK
U2 - 10.1049/hve2.12405
DO - 10.1049/hve2.12405
M3 - Article
AN - SCOPUS:85183172739
SN - 2397-7264
VL - 9
SP - 319
EP - 335
JO - High Voltage
JF - High Voltage
IS - 2
ER -