Ventilation positive pressure intervention effect on indoor air quality in a school building with moisture problems

Research output: Contribution to journalArticleScientificpeer-review

Researchers

Research units

  • University of Szeged
  • Tallinn University of Technology

Abstract

This case study investigates the effects of ventilation intervention on measured and perceived indoor air quality (IAQ) in a repaired school where occupants reported IAQ problems. Occupants’ symptoms were suspected to be related to the impurities leaked indoors through the building envelope. The study’s aim was to determine whether a positive pressure of 5–7 Pa prevents the infiltration of harmful chemical and microbiological agents from structures, thus decreasing symptoms and discomfort. Ventilation intervention was conducted in a building section comprising 12 classrooms and was completed with IAQ measurements and occupants’ questionnaires. After intervention, the concentration of total volatile organic compounds (TVOC) and fine particulate matter (PM2.5) decreased, and occupants’ negative perceptions became more moderate compared to those for other parts of the building. The indoor mycobiota differed in species composition from the outdoor mycobiota, and changed remarkably with the intervention, indicating that some species may have emanated from an indoor source before the intervention.

Details

Original languageEnglish
Article number230
Number of pages23
JournalInternational Journal of Environmental Research and Public Health
Volume15
Issue number2
Publication statusPublished - 1 Feb 2018
MoE publication typeA1 Journal article-refereed

    Research areas

  • Indoor air quality, Indoor air questionnaire, Moisture damage, Mycobiota, Positive pressure, Ventilation

Download statistics

No data available