Abstract

The green energy transition threatens stability of the power grid due to associated reduction in grid synchronous inertia. Primary frequency control (PFC) can compensate for the challenge; however, sufficient procurement of primary frequency capacity could depend on more extensive employment of demand-side loads for PFC. Ventilation fans in particular present a promising class of such loads because of ubiquity of variable-frequency drives and relatively slow thermal and ventilation dynamics of indoor spaces. This research proposes a novel method for PFC by an air handling unit: the open loop control is shown to have favorable dynamic characteristics, and its impact on indoor climate is shown to be tolerable. This study suggests that the largely unused primary frequency capacity of ventilation fans could be exploited to provide primary frequency response for low inertia power grids.
Original languageEnglish
Article number3777
Number of pages15
JournalEnergies
Volume17
Issue number15
DOIs
Publication statusPublished - Aug 2024
MoE publication typeA1 Journal article-refereed

Keywords

  • air handling unit
  • frequency containment reserve
  • primary frequency control
  • variable-frequency drive