Abstract
In this work, measured energy use of the building space heating, ventilation supply air heating, appliances and lighting is compared against simulated energy use modelled in IDA ICE. As built energy need and detailed measured input data is applied in building model calibration procedure. Calibrated building model energy performance is studied in both measured and test reference year climate conditions. Previously modelled as built plant automation and implemented control logics are compared against measured. Geothermal plant in this study consists of heat pump, solar collectors, boreholes and energy piles. Heat pump SCOP estimated by post processing according to heat pump manufacturer's performance map is compared against measured SCOP on the monthly basis. Opinion on actual plant operation is given and energy performance improvement potential is quantified. Important parameters for successful building model calibration are presented. Building compliance with Finland NZEB requirements are assessed. The results show good match with measured energy use after the model calibration.
Original language | English |
---|---|
Article number | 16012 |
Number of pages | 11 |
Journal | E3S Web of Conferences |
Volume | 172 |
DOIs | |
Publication status | Published - 30 Jun 2020 |
MoE publication type | A4 Conference publication |
Event | Nordic Symposium on Building Physics - Tallinn, Estonia Duration: 6 Sept 2020 → 9 Sept 2020 Conference number: 12 https://irbest.eu/en/news/news/nsb-2020-tallinn-simpozium-eng |