TY - JOUR
T1 - Energy performance, indoor air quality and comfort in new nearly zero energy day-care centres in northern climatic conditions
AU - Kuusk, Kalle
AU - Ahmed, Kaiser
AU - Lolli, Nicola
AU - Johansson, Jan
AU - Hasu, Tero
AU - Lien, Anne Gunnarshaug
AU - Arumägi, Endrik
AU - Kalbe, Kristo
AU - Hallik, Jaanus
AU - Kurnitski, Jarek
AU - Kalamees, Targo
PY - 2019/4/17
Y1 - 2019/4/17
N2 - The European energy policy pushes the member states to transform building stock into nearly Zero-Energy Buildings (nZEB). This paper is focused on data collected from existing nZEB day-care centres, in order to be able to assess possible differences between predicted and actual energy and indoor environmental performance. Building structures, service systems and the indoor climate and energy performance of five day-care centres were investigated in Estonia, Finland and Norway. Indoor climate condition measurements showed that in general, the thermal environment and indoor air quality corresponded to the highest indoor climate categories I and II (EN 15251). Building heating and ventilation systems in studied buildings are working without major problems. Good indoor climate conditions were also reflected in the occupant satisfaction questionnaires. For most of the studied buildings, over 80% of the people marked all indoor environment condition parameters (thermal comfort, indoor air quality, acoustics, odour and illuminance) acceptable. The thermal environment in the cooling season was reported problematic because it was lower than the minimum temperature for indoor climate category II. Energy consumption analysis showed that measured real energy use was higher, or even significantly higher, than the energy use calculated during the design phase. Potential causes of the higher actual energy consumption are caused by differences of measured and designed solutions, methodology of the energy calculations, and the differences in user behaviour. Lessons learnt from previously constructed day-care centres can be utilised in the planning and design of new nZEBs.
AB - The European energy policy pushes the member states to transform building stock into nearly Zero-Energy Buildings (nZEB). This paper is focused on data collected from existing nZEB day-care centres, in order to be able to assess possible differences between predicted and actual energy and indoor environmental performance. Building structures, service systems and the indoor climate and energy performance of five day-care centres were investigated in Estonia, Finland and Norway. Indoor climate condition measurements showed that in general, the thermal environment and indoor air quality corresponded to the highest indoor climate categories I and II (EN 15251). Building heating and ventilation systems in studied buildings are working without major problems. Good indoor climate conditions were also reflected in the occupant satisfaction questionnaires. For most of the studied buildings, over 80% of the people marked all indoor environment condition parameters (thermal comfort, indoor air quality, acoustics, odour and illuminance) acceptable. The thermal environment in the cooling season was reported problematic because it was lower than the minimum temperature for indoor climate category II. Energy consumption analysis showed that measured real energy use was higher, or even significantly higher, than the energy use calculated during the design phase. Potential causes of the higher actual energy consumption are caused by differences of measured and designed solutions, methodology of the energy calculations, and the differences in user behaviour. Lessons learnt from previously constructed day-care centres can be utilised in the planning and design of new nZEBs.
KW - Day-care centres
KW - Energy consumption
KW - Indoor air quality
KW - Indoor thermal conditions
KW - nZEB
KW - Occupant satisfaction
UR - http://www.scopus.com/inward/record.url?scp=85069907042&partnerID=8YFLogxK
U2 - 10.5755/j01.sace.24.1.22180
DO - 10.5755/j01.sace.24.1.22180
M3 - Article
AN - SCOPUS:85069907042
SN - 2029-9990
VL - 24
SP - 7
EP - 16
JO - Journal of Sustainable Architecture and Civil Engineering
JF - Journal of Sustainable Architecture and Civil Engineering
IS - 1
ER -