Analysis of partial discharge signals in medium voltage XLPE cables

Zeeshan Ahmed, Ghulam Amjad Hussain, Matti Lehtonen, Lukas Varacka, Jozef Kudelcik

Research output: Chapter in Book/Report/Conference proceedingConference article in proceedingsScientificpeer-review

21 Citations (Scopus)

Abstract

The partial discharge measurements have been widely used in the field of insulation diagnostics. The presence of partial discharges inside the cable indicates the degradation of insulation material. This paper deals with the development of insulation diagnostic method based on the partial discharge (PD) measurements. The useful information about the partial discharge activity and insulation defects is extracted by the experimental results. Artificial cavity was introduced inside the medium voltage XLPE cable by using the traditional needleplane configuration. The statistical characteristics formulated with the help of PRPDA technique and ultra-wideband discharge characteristics by using HFCT sensor was studied and analyzed. Paper is related to study about the partial discharge phenomenon in detail. The aim is to interpret the variations in the partial discharge characteristics over the insulation ageing period in terms of physical phenomenon's taking place in PD sources. The results of this work are based on the partial discharge measurements for lifetime tests conducted over the medium voltage (MV) XLPE cable samples at high voltage laboratory.

Original languageEnglish
Title of host publicationProceedings of the 17th International Scientific Conference on Electric Power Engineering, EPE 2016
PublisherIEEE
Number of pages6
ISBN (Electronic)978-1-5090-0908-4, 978-1-5090-0907-7
ISBN (Print)978-1-5090-0909-1
DOIs
Publication statusPublished - 25 Jul 2016
MoE publication typeA4 Conference publication
EventInternational Scientific Conference Electric Power Engineering - Prague, Czech Republic
Duration: 16 May 201618 May 2016
Conference number: 17

Conference

ConferenceInternational Scientific Conference Electric Power Engineering
Abbreviated titleEPE
Country/TerritoryCzech Republic
CityPrague
Period16/05/201618/05/2016

Keywords

  • degradation
  • diagnostics
  • insulation
  • monitoring
  • XLPE insulated cables

Fingerprint

Dive into the research topics of 'Analysis of partial discharge signals in medium voltage XLPE cables'. Together they form a unique fingerprint.