Indoor occupancy ground truth dataset with variable ventilation

Dataset

Description

Indoor occupancy ground truth dataset with variable ventilation.

Overview

This dataset contains measurements from a controlled laboratory experiment studying indoor air quality (IAQ) and occupancy detection in a simulated Finnish office environment. The dataset contains several IAQ sensors, and the ventilation rate is also measured. Ventilation rate varies in the dataset.

The data was collected to test ventilation control based on occupant count estimates from an ML model.

Experimental Setup

Test Environment



Location: Laboratory designed to simulate a typical Finnish office room

Capacity: Up to 4 occupants

Dimensions: 2.69m (height) × 2.71m (width) × 3.0m (length)


Ventilation System



Type: Variable Air Volume (VAV) system

Control: Modulated airflow rates via Air Handling Unit (AHU)

Configuration: Supply and exhaust setpoint flows maintained at equal rates

Temperature control: Temperature maintained by chiller


Sensors and Measurements




Sensor
Measurement
Accuracy




Miran DLS IAQ.THB-H9+CO2
CO₂ (ppm)
±30 ppm


 
Pressure (mbar)
±1.0 mbar


 
Temperature (°C)
±0.3°C


 
Relative Humidity (%)
±2.5%


HDK - Duct CO₂ transmitter / controller
CO₂ (ppm)
±40 ppm +3 %


Lindab FTCU
Airflow (l/s)
±5%


Steinel HPD2
Occupant count
 






** Miran DLS IAQ.THB-H9+CO2 placed inside the room**: 1.75 meters

** HDK - Duct CO₂ transmitter / controller: Measures supply and exhaust air CO₂ inside the duct.

Occupancy ground truth: Camera-based computer vision occupant counting sensors, and later manually recorded.


Dataset Details

The training data includes multiple ventilation control strategies, and in the test data, we controlled ventilation according to occupant count. 

Occupancy-based control:



Base ventilation: 3 l/s (unoccupied)

Per-person increment: 6 l/s per detected occupant

Update frequency: Every 5 minutes


Training Data

Note that the test room was renovated after March 2025, including the addition of thermal insulation to the walls.





Training data 1: February 2024 - March 2025



Duration: 5 days, 21 hours

The collection saw various usage, meaning that the data may be noisier than the training data 2.

Sensors: Miran DLS IAQ.THB-H9+CO2, 2x Lindab FTCU, Steinel HPD2

Occupancy data: Camera-based occupancy ground truth





Training data 2: October 2025 - November 2025



Duration: 2 days, 20 hours days

Sensors: Miran DLS IAQ.THB-H9+CO2, 2x Lindab FTCU, 2x HDK - Duct CO₂ transmitter / controller

Occupancy data: Manually recorded occupancy ground truth




Ventilation test



Period 2: October 2025 - November 2025



Duration: 24 hours

Collection method: Manually recorded occupancy ground truth




Testing Data



Ventilation control testing: 23 hours, 50 minutes


Funding

This research was funded by the Promotion Centre for Electrical Engineering and Energy Efficiency (STEK ry) grant KITSI2.0.
Date made available19 Jan 2026
PublisherZenodo

Dataset Licences

  • CC-BY-4.0